Product Specifications
Technical Parameters
| Parameter | Value |
|---|---|
| Product Model | NXB-63M |
| Product Type | Magnetic-only circuit breaker |
| Rated Current In | 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Rated Operational Voltage Ue | 230V AC for 1P; 400V AC for 2P, 3P and 4P |
| Rated Insulation Voltage Ui | 500V |
| Rated Frequency | 50Hz |
| Instantaneous Tripping Characteristic | C type: Ii = 8In; D type: Ii = 12In |
| Number of Poles | 1P, 2P, 3P, 4P |
| Mechanical Endurance | 20,000 operating cycles |
| Electrical Endurance | 10,000 operating cycles |
| Rated Ultimate Short-Circuit Breaking Capacity Icu | 6kA |
| Rated Service Short-Circuit Breaking Capacity Ics | 6kA |
| Rated Impulse Withstand Voltage Uimp | 4kV |
| Maximum Frame Rated Current | 63A |
Maximum Power Loss per Pole
| Rated Current In | Maximum Power Loss per Pole |
|---|---|
| In ≤ 10A | 3W |
| 10A < In ≤ 16A | 3.5W |
| 16A < In ≤ 25A | 4.5W |
| 25A < In ≤ 32A | 6W |
| 32A < In ≤ 40A | 7.5W |
| 40A < In ≤ 50A | 9W |
| 50A < In ≤ 63A | 13W |
Derating Factors for Multiple Devices Installed Side by Side
| Number of Devices | Recommended Rated Current |
|---|---|
| ≤3 devices | (0.90–0.95)In |
| 4–6 devices | (0.80–0.86)In |
| 7–9 devices | (0.76–0.78)In |
| >9 devices | 0.76In |
Rated Current Correction Factors for High-Altitude Operation
| Altitude | Corrected Rated Current |
|---|---|
| ≤2000m | In |
| 3000m | 0.96In |
| 4000m | 0.94In |
| 5000m | 0.92In |
The recommended selection values and correction factors are for reference only. Final selection should be based on ambient temperature, installation conditions, load characteristics and actual operating conditions.
尺寸图

Product Overview
The NXB-63M is a magnetic-only circuit breaker designed for short-circuit protection in low-voltage distribution circuits operating at AC 50Hz. It is available with rated currents of 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A and 63A, and can be supplied in 1P, 2P, 3P and 4P configurations. The rated operational voltage is 230V AC for the 1P version and 400V AC for the 2P, 3P and 4P versions. The rated insulation voltage is 500V. Two instantaneous tripping characteristics are available: C type with an instantaneous tripping current of 8In, and D type with an instantaneous tripping current of 12In. The appropriate characteristic should be selected according to the starting current and operating characteristics of the connected load. The rated ultimate short-circuit breaking capacity and rated service short-circuit breaking capacity are both 6kA. The rated impulse withstand voltage is 4kV. The product has a mechanical endurance of 20,000 operating cycles and an electrical endurance of 10,000 operating cycles. When multiple devices are installed side by side or when the product is used at high altitude, the rated current should be adjusted according to the number of adjacent devices, altitude, ambient temperature and actual operating conditions.