Product Specifications
Technical Parameters
| Parameter | Value |
|---|---|
| Product Model | NXB-63H |
| Product Type | Miniature circuit breaker |
| Rated Current In | 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Rated Operational Voltage Ue | 230V AC for 1P and 1P+N; 400V AC for 2P, 3P, 3P+N and 4P |
| Rated Insulation Voltage Ui | 500V |
| Rated Frequency | 50Hz |
| Instantaneous Tripping Characteristics | B, C, D |
| Number of Poles | 1P, 1P+N, 2P, 3P, 3P+N, 4P |
| Mechanical Endurance | 20,000 operating cycles |
| Electrical Endurance | 10,000 operating cycles |
| Rated Short-Circuit Breaking Capacity Icn | 10,000A |
| Service Short-Circuit Breaking Capacity Ics | 7,500A |
| Rated Impulse Withstand Voltage Uimp | 4kV |
| Maximum Frame Rated Current | 63A |
Maximum Power Loss per Pole
| Rated Current In | Maximum Power Loss per Pole |
|---|---|
| In ≤ 10A | 3W |
| 10A < In ≤ 16A | 3.5W |
| 16A < In ≤ 25A | 4.5W |
| 25A < In ≤ 32A | 6W |
| 32A < In ≤ 40A | 7.5W |
| 40A < In ≤ 50A | 9W |
| 50A < In ≤ 63A | 13W |
Derating Factors for Multiple Devices Installed Side by Side
| Number of Devices | Recommended Rated Current |
|---|---|
| ≤3 devices | (0.90–0.95)In |
| 4–6 devices | (0.80–0.86)In |
| 7–9 devices | (0.76–0.78)In |
| >9 devices | 0.76In |
Rated Current Correction Factors for High-Altitude Operation
| Altitude | Corrected Rated Current |
|---|---|
| ≤2000m | In |
| 3000m | 0.96In |
| 4000m | 0.94In |
| 5000m | 0.92In |
The recommended selection values and correction factors are for reference only. Final product selection should be based on ambient temperature, installation conditions, load characteristics and actual operating conditions.
尺寸图

Product Overview
The NXB-63H is a miniature circuit breaker designed to protect low-voltage distribution circuits and electrical equipment against overload and short-circuit faults. It is suitable for AC 50Hz systems and is available with rated currents of 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A and 63A. The rated operational voltage is 230V AC for 1P and 1P+N versions, and 400V AC for 2P, 3P, 3P+N and 4P versions. The rated insulation voltage is 500V. The product is available with B, C and D instantaneous tripping characteristics, allowing selection according to the circuit type, load starting current and actual operating conditions. Pole configurations include 1P, 1P+N, 2P, 3P, 3P+N and 4P, making the product suitable for different single-phase and multiphase distribution systems. The rated short-circuit breaking capacity Icn is 10,000A, while the service short-circuit breaking capacity Ics is 7,500A. The rated impulse withstand voltage is 4kV. Mechanical endurance is 20,000 operating cycles, and electrical endurance is 10,000 operating cycles. When several devices are installed side by side or when the product is used at high altitude, the rated current should be adjusted according to the number of adjacent devices and the installation altitude. The recommended correction factors are for reference only; final selection should also consider ambient temperature, installation conditions, load characteristics and actual operating conditions.