Technical Parameters
| Parameter | Value |
|---|---|
| Product Model | NB8-63H |
| Rated Current | 1 A, 2 A, 3 A, 4 A, 6 A, 10 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A |
| Rated Voltage | 230/400 V |
| Rated Frequency | 50 Hz |
| Number of Poles | 1P, 1P+N, 2P, 3P, 3P+N, 4P |
| Mechanical Life | 20,000 operations |
| Electrical Life | 10,000 operations |
| Rated Short-Circuit Breaking Capacity | 10,000 A |
| Service Short-Circuit Breaking Capacity | 7,500 A |
| Rated Insulation Voltage | 500 V |
| Rated Impulse Withstand Voltage | 6 kV |
| Dielectric Test Voltage | 2,000 V, 50 Hz, 1 minute |
| Resistance to Damp Heat | 28-cycle test |
| Vibration Resistance | Suitable for locations without significant vibration or impact |
| Terminal Type | Pillar terminal |
| Minimum Conductor Cross-Section | 1 mm² |
| Maximum Conductor Cross-Section | 25 mm² |
| Standard Tightening Torque | 2 N·m |
| Maximum Permissible Torque | 2.5 N·m |
| Conductor Insertion Depth | 13 mm |
| Reference Temperature | 30°C |
| Operating Temperature | -35°C to +70°C |
| Storage Temperature | -35°C to +85°C |
| Maximum Operating Altitude | 2,000 m |
| Tripping Type | Thermal-magnetic trip |
| Electromagnetic Trip Curve | B curve: 3In–5In; C curve: 5In–10In; D curve: 10In–16In |
| Enclosure Flame-Retardant Rating | V-0 |
| Incoming Wiring Direction | Top or bottom |
| Mounting Method | TH35-7.5 standard DIN rail |
| Pollution Degree | 3 |
| Degree of Protection | IP20B when directly installed; IP40B when installed in a distribution enclosure |
| Optional Accessories | S9, V9, XF9, XF9J, OVT-1, OUVT-1 |
尺寸

Product Overview
The NB8-63H miniature circuit breaker is mainly designed for AC 50 Hz terminal distribution circuits with a rated voltage up to 400 V and a rated current up to 63 A. It is widely used in commercial office buildings, residential properties, and general industrial facilities. The circuit breaker automatically disconnects the circuit in the event of overload or short circuit, providing reliable protection for distribution lines and connected electrical equipment. It may also be used for infrequent switching of circuits under normal operating conditions. The NB8-63H is available in 1P, 1P+N, 2P, 3P, 3P+N, and 4P configurations, with rated currents ranging from 1 A to 63 A. It is suitable for both single-phase and three-phase terminal distribution systems. Its rated short-circuit breaking capacity reaches 10,000 A, while its service short-circuit breaking capacity is 7,500 A, making it suitable for applications requiring higher fault-current interruption capability. The product is available with B, C, and D tripping characteristics. The B curve is suitable for resistive loads and circuits with low inrush current, the C curve is suitable for lighting, socket circuits, and general inductive loads, while the D curve is intended for motors, transformers, and other equipment with high starting currents. The NB8-63H uses a thermal-magnetic tripping mechanism, supports both top and bottom incoming wiring, and is designed for installation on a TH35-7.5 standard DIN rail. It features a compact structure, convenient installation, reliable operation, high breaking capacity, and a long service life. Optional accessories can be added for auxiliary indication, alarm signaling, shunt tripping, and overvoltage or undervoltage protection.
Need Help?