Product Specifications
Product Series
| Parameter | Value |
|---|---|
| Series | Acti9 Pro |
| Product Name | iC65M Circuit Breaker |
| Trip Curve | B, C, D curves |
| Operating Frequency | AC 50/60 Hz |
Standards
| Parameter | Value |
|---|---|
| Chinese Standard | GB/T 14048.2 |
| International Standard | IEC/EN 60947-2 |
| UL Standard | UL 1077 |
Product Functions
| Function | Description |
|---|---|
| Short-circuit protection | Supported |
| Overload protection | Supported |
| Isolation function | Supported |
| Clear fault disconnection indication | Supported |
| Fault trip indication | Red indication on the front viewing window |
Breaking Capacity Icu
| Rated Current In | 12 |
220 |
380 |
440V | Service Breaking Capacity Ics |
|---|---|---|---|---|---|
| 1~4 A | 100 kA | 100 kA | 100 kA | 70 kA | 100% Icu |
| 6~25 A | 50 kA | 50 kA | 25 kA | 20 kA | 50% Icu |
| 32~40 A | 50 kA | 50 kA | 25 kA | 15 kA | 50% Icu |
| 50~63 A | 30 kA | 30 kA | 25 kA | 10 kA | Icu=30kA: Ics=37.5% Icu; Icu=25kA: Ics=40% Icu; Icu=10kA: Ics=50% Icu |
UL 1077 Breaking Capacity
| Poles | Rated Voltage | Rated Current | Breaking Capacity |
|---|---|---|---|
| 1P | 120 V / 240 VAC | 1~63 A | 10 kA |
| 2P/3P | 240 VAC | 1~63 A | 10 kA |
| 2P/3P/4P | 277 V / 480 VAC | 1~63 A | 6 kA |
Wiring Parameters
| Rated Current | Screw Size | Rated Torque | Limit Torque | National Standard Rated Torque | Solid Copper Wire | Flexible Wire or Ferruled Terminal |
|---|---|---|---|---|---|---|
| 1~25 A | M5 | 2.5 N·m | 5.1 N·m | 2 N·m | 1~25 mm² | 1~16 mm² |
| 32~63 A | M6.5 | 3.5 N·m | 5.6 N·m | 3.5 N·m | 1~35 mm² | 1~25 mm² |
UL 1077 Wiring Parameters
| Rated Current | Screw Size | Rated Torque | National Standard Rated Torque | 75°C Copper Wire |
|---|---|---|---|---|
| 1~25 A | M5 | 2.5 N·m | 2 N·m | AWG 14-10 |
| 32~63 A | M6.5 | 3.5 N·m | 3.5 N·m | AWG 8-4 |
Main Technical Parameters
| Parameter | Value |
|---|---|
| Rated Insulation Voltage Ui | 500 V AC |
| Pollution Degree | 3 |
| Rated Impulse Withstand Voltage Uimp | 6 kV |
| Reference Calibration Temperature | 50°C |
| B Curve Magnetic Trip | 4In ±20% |
| C Curve Magnetic Trip | 8In ±20% |
| D Curve Magnetic Trip | 12In ±20% |
| Utilization Category | A |
| Current Limiting Class | 3 |
Other Parameters
| Parameter | Value |
|---|---|
| Protection Degree of Breaker Body | IP20 |
| Protection Degree When Installed in Distribution Box | IP40 |
| Insulation Class | II |
| Electrical Endurance | 10,000 cycles |
| Mechanical Endurance | 20,000 cycles |
| Overvoltage Category | IV |
| Operating Ambient Temperature | -40°C ~ +70°C |
| Storage Ambient Temperature | -40°C ~ +85°C |
| Damp Heat Resistance | Class 2, relative humidity 95% at 55°C |
| Padlock for 1P/2P | 1 piece |
| Padlock for 3P/4P | 2 pieces |
Weight
| Type | Average Weight |
|---|---|
| 1P | 125 g |
| 2P | 250 g |
| 3P | 375 g |
| 4P | 500 g |
Product Overview
The iC65M circuit breaker belongs to the Acti9 Pro series of miniature circuit breakers and is available with B, C, and D trip curves to meet the protection requirements of different types of loads. The product complies with GB/T 14048.2, IEC/EN 60947-2, and UL 1077 standards, and is suitable for AC 50/60Hz power distribution systems. It provides short-circuit protection, overload protection, and isolation function, with clear indication of fault disconnection. The front viewing window displays a red indication when the circuit breaker trips due to a fault, helping maintenance personnel quickly identify the device status on site. The iC65M is available in 1P, 2P, 3P, and 4P configurations, with rated currents from 1A to 63A. Depending on voltage, pole configuration, and rated current, the breaking capacity can reach up to 100kA. The product is suitable for standard distribution boxes and terminal distribution systems, including residential buildings, commercial buildings, industrial control cabinets, and power distribution equipment.
Need Help?
Send us the model number or purchase list. We'll check price and availability.