Product Specifications
CDB6i-125 Moulded Case Circuit Breaker
The CDB6i-125 series moulded case circuit breaker is a high-performance protection device designed for low-voltage AC distribution systems. It is widely used in industrial equipment, building power distribution, and electrical control systems.
The circuit breaker integrates overload protection, short circuit protection, control, and isolation functions, effectively protecting electrical circuits and equipment from damage caused by overload currents and short circuit faults.
The CDB6i-125 series supports rated current options of 63A, 80A, 100A, and 125A, with pole configurations including 1P, 2P, 3P, and 4P. The rated operating voltage supports 230/240VAC for single-pole applications and 400/415VAC for multi-pole applications.
The product adopts thermal-magnetic tripping technology and supports C and D tripping curves:
- C curve is suitable for standard loads and distribution circuit protection.
- D curve is suitable for motors and equipment with high starting currents.
With a modular design, the circuit breaker can be easily installed on standard 35mm DIN rails. It features U-type terminals with a maximum cable capacity of 50mm² and supports various accessories, including OF auxiliary contacts, SD alarm contacts, MX+OF shunt release, overvoltage release, and undervoltage release.
The CDB6i-125 series is widely applied in industrial control cabinets, mechanical equipment, low-voltage distribution systems, building electrical systems, and OEM complete equipment.
Product Features
- Provides overload protection, short circuit protection, control, and isolation functions
- Supports high current applications from 63A to 125A
- Available in 1P, 2P, 3P, and 4P configurations
- Supports C and D tripping curves
- Breaking capacity up to 10kA
- Modular structure with standard DIN rail mounting
- Supports multiple electrical accessories
- Suitable for industrial and low-voltage distribution applications
Applications
- Industrial power distribution systems
- Automation equipment
- Electrical control cabinets
- Building low-voltage distribution systems
- OEM complete equipment
Technical Parameters
| Parameter | Value | Unit |
|---|---|---|
| Product Series | CDB6i-125 | - |
| Product Type | Moulded Case Circuit Breaker | - |
| Rated Current In | 63, 80, 100, 125 | A |
| Number of Poles | 1P, 2P, 3P, 4P | - |
| Rated Operating Voltage Ue | 1P: 230/240 AC; 2P, 3P, 3P+N, 4P: 400/415 AC | V |
| Rated Insulation Voltage Ui | 500 | V |
| Rated Short-Circuit Capacity Icn | 10 | kA |
| Rated Impulse Withstand Voltage Uimp | 4 | kV |
| Dielectric Test Voltage | 2kV (50Hz, 1 minute) | - |
| Utilization Category | A | - |
| Isolation Function | Available | - |
| Pollution Degree | 2 | - |
| Tripping Type | Thermal Magnetic Release | - |
| Tripping Curve | C Curve, D Curve | - |
| Product Standard | IEC/EN 60947-2, GB/T 14048.2 | - |
| Certifications | CCC, CE, CB, SEMKO | - |
Tripping Characteristics
| Type | Characteristic |
|---|---|
| C Curve | Suitable for standard loads and distribution circuits, instantaneous tripping range 5~10In |
| D Curve | Suitable for motors and high inrush current loads, instantaneous tripping range 10~14In |
Mechanical Characteristics
| Parameter | Value | Unit |
|---|---|---|
| Handle Color | Red | - |
| Contact Position Indicator | Red indicator showing ON/OFF status | - |
| Mechanical Endurance | 20000 | Operations |
| Electrical Endurance | 6000 (In≤100A); 4000 (In>100A) | Operations |
| Protection Degree | IP40 inside distribution box; IP20 direct installation | - |
| Mechanical Shock Resistance | 30g, 3 impacts, duration 11ms | - |
| Vibration Resistance | IEC/EN 60068-2-6 | - |
| Damp Heat Resistance | Category 2, 28-day cycle | - |
| Reference Ambient Temperature | 30 | °C |
| Operating Temperature | -35~70 | °C |
| Storage Temperature | -40~85 | °C |
Installation Characteristics
| Parameter | Value | Unit |
|---|---|---|
| Terminal Type | U-type terminal | - |
| Maximum Cable Capacity | 50 | mm² |
| Maximum Tightening Torque | 3.5 | N·m |
| Installation Method | Standard 35mm DIN rail mounting | - |
| Wiring Direction | Top in, bottom out | - |
| Recommended Tool | Phillips screwdriver or flat screwdriver | - |
Compatible Accessories
| Accessory | Function |
|---|---|
| OF | Auxiliary Contact |
| SD | Alarm Contact |
| MX+OF | Shunt Release + Auxiliary Contact |
| Overvoltage Release | Overvoltage Protection |
| Undervoltage Release | Undervoltage Protection |
尺寸图

Need Help?
Send us the model number or purchase list. We'll check price and availability.